Final | 10/10/2007 | 10/11/2007 | 10/11/2007 | A | PASS |
Pat Lass
|
|
|
CURTIS ###-####
|
Electrical Rough-In | 10/3/2007 | 10/4/2007 | 10/4/2007 | P | CANC |
Jim Schmer
|
|
|
ceiling inspection / final if possible Phone #: ###-#### Internet Inspection Request from: Curtis Dunham ok corr. made jms
|
Final | 9/27/2007 | 9/27/2007 | 9/27/2007 | A | FAIL |
Jack Frank
|
|
|
ceiling for cover and final if possible second number if needed ###-#### Shane Phone #: ###-#### Internet Inspection Request from: Curtis Dunham called left message, corr. not made also zip cord on pendent light shall be in the box , it is through a ko back off box and taped to the bar hanger
|
Final | 9/25/2007 | 9/25/2007 | 9/25/2007 | P | FAIL |
Jack Frank
|
|
|
ceiling inspection and final if possible Phone #: ###-#### Internet Inspection Request from: Curtis Dunham corr. 330.30 shall secure all MC within 12" of boxes, 110.12(A) shall seal all unused openings KOs met contr
|
Final | 9/19/2007 | 9/20/2007 | 9/20/2007 | A | FAIL |
Bob Reichert
|
|
|
Above ceiling and final inspection. Phone #: ###-#### Internet Inspection Request from: Curtis Dunham corrections not all made, called contr to fix, initialed on correction notice, told contractor they can't use raceways for support for low voltage wires
|
Electrical Rough-In | 9/3/2007 | 9/4/2007 | 9/4/2007 | P | FAIL |
Jack Frank
|
|
|
inspection for ceiling cover Phone #: ###-#### Internet Inspection Request from: Curtis Dunham corr called 110.12(A) seal KOs, 314.25 covers for all boxes, 314.23(D) and 300.11 needs support wires for boxes in grid, bld-0922 support all low voltage cables laying on grid
|
Electrical Rough-In | 7/7/2007 | 7/9/2007 | 7/9/2007 | P | PART |
Pat Lass
|
|
|
rough-in above sheet rock ceilings thanks Curtis Phone #: ###-#### Internet Inspection Request from: Curtis Dunham hard lids ok
|
Electrical Rough-In | 6/19/2007 | 6/19/2007 | 6/19/2007 | P | PART |
Pat Lass
|
|
|
walls only Phone #: ###-#### Internet Inspection Request from: Curtis Dunham wALLS OK
|