Final | 10/4/2007 | 10/4/2007 | 10/4/2007 | P | PASS |
Bob Reichert
|
|
|
Would like a late afternoon inspection. Shane Vanleuven is contact. ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis ok to final, will permit garage separately
|
Rough-In Permanent Service | 7/2/2007 | 7/3/2007 | 7/3/2007 | A | PASS |
Bob Reichert
|
|
|
Contact Shane Vanleuven re-inspect for service and mech. room that failed. Phone #: ###-#### Internet Inspection Request from: Debby Ellis ric mech room ok, corrections made, p/s o/h rec ok
|
Rough-In Permanent Service | 6/28/2007 | 6/29/2007 | 6/29/2007 | A | FAIL |
Bob Reichert
|
|
|
Shane Vanleuven / inspect for service and Mech. room. Phone #: ###-#### Internet Inspection Request from: Debby Ellis called left corr notice, 334.30 nm cable shall be strapped within 12" of box, 362.26 ent shall not have over 360 degree bends, 250.52(A)(1) shall use water pipe within 5' of entering building for grounding electrode to service, 110.14(A) ground clamp shall be tight, BCC old exst gnd rod shall be abandoned or used with proper clamp
|
Electrical Rough-In | 6/19/2007 | 6/19/2007 | 6/19/2007 | P | PART |
Bob Reichert
|
|
|
Shane Vanleuven ###-#### Thank-You Phone #: ###-#### Internet Inspection Request from: Debby Ellis ric basement except mech room ok
|