Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE07-02299
StatusFinaled
Name LOFTHOUSE ELECTRIC
Site Address 2901 W STATE ST
Project NameFAMILY DOLLAR STORE PLAZA
Customer Number 
ePlanReview 
Description
Install 400 amp service, lights & outlets per initial cert of value $10,000///6/26/07 BAS ///final value remains the same per faxed document 11-2-07ps
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/4/20079/5/20079/5/2007APASS
DetailsBob Reichert
Terry; Phone #: ###-#### Internet Inspection Request from: Hattie James corrections made, ok to final, signed struct card only
Final8/31/20079/4/20079/4/2007AFAIL
DetailsJack Frank
Terry; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
corr. not made still needs ceiling tiles removed met contr
Final8/30/20078/30/20078/30/2007PFAIL
DetailsJack Frank
terry; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt
314,23 all boxes shall be supported 362.30&330.30 all ent and mc shall secured at boxes and supported , remove ceiling tiles, install show windoe outlets, support all fixtures with wires called left message
Permanent Service8/10/20078/13/20078/13/2007APASS
DetailsPat Lass
terry Phone #: ###-####
P/S U/g N Ok
Permanent Service8/9/20078/9/20078/9/2007PFAIL
DetailsPat Lass
terry Phone #: ###-####
no SER allowed in conduit, needs 3/0 copper or 250KC mil for 400 amp feeder
support pvc
Electrical Rough-In7/2/20077/2/20077/2/2007PPART
DetailsJack Frank
terry; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
conference on p/s no SER allowed in conduit, needs 3/0 copper or 250KC mil for 400 amp feeder, r/i for back office and restrm area ok walls and hard ceilings
Electrical Rough-In6/29/20077/2/20077/2/2007ACANC
DetailsBob Reichert
terry Phone #: ###-#### see conf
Conference7/2/20077/2/20077/2/2007ADONE
DetailsBob Reichert
terry Phone #: ###-#### met contr, reviewed 6" free conductor, not using valley of 2x4 steel stud for securing mc, make-up, inspections required, this is first time contr working in city