Final | 9/4/2007 | 9/5/2007 | 9/5/2007 | A | PASS |
Bob Reichert
|
|
|
Terry; Phone #: ###-#### Internet Inspection Request from: Hattie James corrections made, ok to final, signed struct card only
|
Final | 8/31/2007 | 9/4/2007 | 9/4/2007 | A | FAIL |
Jack Frank
|
|
|
Terry; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr. not made still needs ceiling tiles removed met contr
|
Final | 8/30/2007 | 8/30/2007 | 8/30/2007 | P | FAIL |
Jack Frank
|
|
|
terry; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt 314,23 all boxes shall be supported 362.30&330.30 all ent and mc shall secured at boxes and supported , remove ceiling tiles, install show windoe outlets, support all fixtures with wires called left message
|
Permanent Service | 8/10/2007 | 8/13/2007 | 8/13/2007 | A | PASS |
Pat Lass
|
|
|
terry Phone #: ###-#### P/S U/g N Ok
|
Permanent Service | 8/9/2007 | 8/9/2007 | 8/9/2007 | P | FAIL |
Pat Lass
|
|
|
terry Phone #: ###-#### no SER allowed in conduit, needs 3/0 copper or 250KC mil for 400 amp feeder support pvc
|
Electrical Rough-In | 7/2/2007 | 7/2/2007 | 7/2/2007 | P | PART |
Jack Frank
|
|
|
terry; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang conference on p/s no SER allowed in conduit, needs 3/0 copper or 250KC mil for 400 amp feeder, r/i for back office and restrm area ok walls and hard ceilings
|
Electrical Rough-In | 6/29/2007 | 7/2/2007 | 7/2/2007 | A | CANC |
Bob Reichert
|
|
|
terry Phone #: ###-#### see conf
|
Conference | 7/2/2007 | 7/2/2007 | 7/2/2007 | A | DONE |
Bob Reichert
|
|
|
terry Phone #: ###-#### met contr, reviewed 6" free conductor, not using valley of 2x4 steel stud for securing mc, make-up, inspections required, this is first time contr working in city
|