Final | 8/2/2007 | 8/2/2007 | 8/2/2007 | P | PASS |
Jack Frank
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook
|
Final | 8/1/2007 | 8/1/2007 | 8/1/2007 | A | FAIL |
Jack Frank
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook corr. called 250.32 needs grd rode for pool equip panel
|
Electrical Rough-In | 7/18/2007 | 7/18/2007 | 7/18/2007 | P | PASS |
William E Thomas
|
|
|
hand rail bonding ###-#### Internet Inspection Request from: Todd Holbrook bonding ok
|
Electrical Rough-In | 7/17/2007 | 7/17/2007 | 7/17/2007 | P | PASS |
Jack Frank
|
|
|
TOM Phone #: ###-#### corr. made Egrid , bond, potting ok
|
Electrical Rough-In | 7/16/2007 | 7/16/2007 | 7/16/2007 | P | FAIL |
Jack Frank
|
|
|
tom Phone #: ###-#### corr do not cover , called wire mesh shall be installed per instruction sheet for pool E grid potting ok
|
Electrical Rough-In | 7/5/2007 | 7/6/2007 | 7/6/2007 | A | PASS |
William E Thomas
|
|
|
underground ###-#### Internet Inspection Request from: Todd Holbrook underground ok
|
Final | 7/5/2007 | 7/6/2007 | 7/5/2007 | A | CANC |
Jack Frank
|
|
|
Underground ###-#### Internet Inspection Request from: Todd Holbrook Inspection cancelled from web by: Todd Holbrook
|
Electrical Rough-In | 7/5/2007 | 7/5/2007 | 7/5/2007 | A | FAIL |
Bob Reichert
|
|
|
Bonding Grid Underground inspection ###-#### Internet Inspection Request from: Todd Holbrook called, left corr notice, nec 110.3(A) lug shall be suitable for installation and use by listing for purpose, 352.26 there shall not be over 360 degree bends in rnc, 680.10 u/g wiring shall not be within 5' of inside wall of pool
|