Permit Information
Permit NumberELE07-02501
StatusFinaled
Name DESERT ELECTRIC
Site Address 1462 S ENTERTAINMENT AVE
Project NameShops at Spectrum Pointe
Customer Number 
ePlanReview 
Description
(Partial bld permit issued for this project. Not able to do work past r/i stage until full building permit is issued) Running branch circuits and lighting per initial cert of value is $38,000//7/16/07 LEG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/21/20079/21/20079/21/2007APASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Dan Surerus looked at equipment, ETL affixed stickers, ok to final, signed occupancy card
Final9/13/20079/14/20079/14/2007ACANC
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Dan Surerus met contr, listing lab got held up, so will call in next week to inspect some of the equipment
Final9/5/20079/5/20079/5/2007APART
DetailsBob Reichert
Temporary Occupancy Phone #: ###-#### Internet Inspection Request from: Dan Surerus signed t/o card need to see installed equipment for to final, corrections made
Final8/30/20078/30/20078/30/2007PFAIL
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Dan Surerus wiring for switches and wall fixtures in patient rms shall meet 517.13(A&B) see added r/i
Electrical Rough-In8/30/20078/30/20078/30/2007PPART
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Dan Surerus ceiling ok for tiles
Electrical Rough-In8/9/20078/9/20078/9/2007PPART
DetailsWilliam E Thomas
Phone #: ###-#### Internet Inspection Request from: Dan Surerus
1. walls and hard lids/soffits only
2. ri ok.
Permanent Service7/26/20077/26/20077/26/2007PPASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Dan Surerus p/s exst meter pak n ok (2 meters)
Permanent Service7/25/20077/26/20077/26/2007AFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Dan Surerus called contr, left corr notice, nec 110.26(F)(1)(b) shall provide protection to avoid damage to elect equip from condensation, leaks or breaks over panel F, BCC addressing shall be correct and posted