Temporary Service | 7/27/2007 | 7/27/2007 | 7/27/2007 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/27/2007 at 8:35:06 AM. Contact: ###-####. corr made, t/s o/h n ok
|
Temporary Service | 7/24/2007 | 7/25/2007 | 7/25/2007 | A | FAIL |
Bob Reichert
|
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang called contr, left corr notice, BCC job id sticker shall be posted, NEC 110.12(A) there shall be no broken or damaged parts- gfci handle tie, 406.8(B)(1)&(2) all recpts shall have in-use covers, 408.4 shall provide circuit directory, 250.53(G) shall drive rod electrode flush with or below grade and protect gec from damage,230.24(B) service conductors shall be 18' over alley
|