Electrical Rough-In | 9/17/2007 | 9/18/2007 | 9/18/2007 | P | FAIL |
Bob Reichert
|
|
|
lawrence Phone #: ###-#### met owner, left corr notice, nec 300.5 pvc shall be min 18" deep to top of conduit, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 314.16(C) only conduit bodies marked by manfacturers with their volume shall be permitted to contain splices and they shall be supported in a rigid manner, 110.14 connections shall be properly installed for ground lugs (use crimping tool)
|
Conference | 7/27/2007 | 7/30/2007 | 7/30/2007 | A | DONE |
Bob Reichert
|
|
|
lawrence- ###-#### talked about ways to do wiring to outbuilding, loads and owner said he may get prices from contractor rather doing his own work
|