Final | 8/8/2007 | 8/8/2007 | 8/8/2007 | P | PASS |
William E Thomas
|
|
|
1. final ok
|
Permanent Service | 8/7/2007 | 8/8/2007 | 8/8/2007 | A | PASS |
William E Thomas
|
|
|
Tony Norton Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer 1. p/s o/h reconnect ok
|
Final | 8/6/2007 | 8/7/2007 | 8/7/2007 | A | CANC |
Jack Frank
|
|
|
Tony Norton did the requested code corrections, please re-inspect Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer Inspection cancelled from web by: Jarrod Clymer
|
Permanent Service | 8/3/2007 | 8/6/2007 | 8/6/2007 | A | FAIL |
Bob Reichert
|
|
|
red tagged by Idaho Power, has been off for 4 years, please inspect Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer called left corr notice, nec 110.12(C) there shall be no broken parts (30 A recpt), 250.64(C) gec shall not be spliced unless by irreversible connection, 110.3(A) all panel screws shall be installed, 408.4 shall provide ckt directory, BCC shall post address, 312.5 shall provide abrasion protection for all conductors entering enclosure
|