Final | 3/21/2008 | 3/21/2008 | 3/21/2008 | P | PASS |
William E Thomas
|
|
|
dennis Phone #: ###-#### . .1. final ok. . . .2. survey note--needs one additional outlet in the kitchen. .
|
Permanent Service | 11/23/2007 | 11/23/2007 | 11/23/2007 | P | PASS |
Pat Lass
|
|
|
reinspect; Dennis Phone #: ###-#### P/S U/G N Ok
|
Electrical Rough-In | 11/21/2007 | 11/23/2007 | 11/23/2007 | A | PASS |
Pat Lass
|
|
|
reinspect; Dennis Phone #: ###-####
|
Electrical Rough-In | 11/19/2007 | 11/20/2007 | 11/20/2007 | A | FAIL |
Jack Frank
|
|
|
Dennis Phone #: ###-#### corr met owner, box fill 11/4" for cables parallel, #4 for GEC, protect cables 6ft attic access, countertop outlet spacing, outside boxes shall be flush with siding, staple cables within 8", note no cutin boxes for new const. , complete makeup
|
Conference | 10/4/2007 | 10/5/2007 | 10/5/2007 | A | DONE |
Jack Frank
|
|
|
dennis NOte: he wil be all morning Phone #: ###-#### ok cow
|