Permit Information
Permit NumberELE07-02766
StatusFinaled
Name GENE A FINCH & JEANETTE Y
Site Address 2718 S VIRGINIA AVE
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/25/200710/2/200710/2/2007PPASS
DetailsMike Kinnear
gene Phone #: ###-#### ok final
Electrical Rough-In9/25/20079/25/20079/25/2007PPART
DetailsWilliam E Thomas
gene Phone #: ###-####
. 1. ok to cover electrode with concrete. .
. 2. other corrections made. .
Electrical Rough-In9/4/20079/7/20079/7/2007AFAIL
DetailsBob Reichert
Gene; Phone #: ###-#### Internet Inspection Request from: Hattie James met owner, left corr notice, nec 250.52(A)(3) shall provide concrete encased electrode encased by minimum 2" concrete, 312.5 all conductors entering enclosure shall have abrasion protection, 110.12(A) unused openings shall be closed, 408.4 circuit directory shall be clear, concise, and explanatory, 250.64(C) grounding electrode conductors shall be continuous without a splice, BCC shall provide electrical identification plate for voltage and amperage for building
Rough-In Permanent Service8/8/20078/10/20078/10/2007ANR
DetailsWilliam E Thomas
gene Phone #: ###-####
1. the trailer needs an electrical identification plate so we know what the voltage and amperage requirements are.