Final | 9/25/2007 | 10/2/2007 | 10/2/2007 | P | PASS |
Mike Kinnear
|
|
|
gene Phone #: ###-#### ok final
|
Electrical Rough-In | 9/25/2007 | 9/25/2007 | 9/25/2007 | P | PART |
William E Thomas
|
|
|
gene Phone #: ###-#### . 1. ok to cover electrode with concrete. . . 2. other corrections made. .
|
Electrical Rough-In | 9/4/2007 | 9/7/2007 | 9/7/2007 | A | FAIL |
Bob Reichert
|
|
|
Gene; Phone #: ###-#### Internet Inspection Request from: Hattie James met owner, left corr notice, nec 250.52(A)(3) shall provide concrete encased electrode encased by minimum 2" concrete, 312.5 all conductors entering enclosure shall have abrasion protection, 110.12(A) unused openings shall be closed, 408.4 circuit directory shall be clear, concise, and explanatory, 250.64(C) grounding electrode conductors shall be continuous without a splice, BCC shall provide electrical identification plate for voltage and amperage for building
|
Rough-In Permanent Service | 8/8/2007 | 8/10/2007 | 8/10/2007 | A | NR |
William E Thomas
|
|
|
gene Phone #: ###-#### 1. the trailer needs an electrical identification plate so we know what the voltage and amperage requirements are.
|