Final | 8/15/2007 | 8/15/2007 | 8/15/2007 | A | PASS |
Mike Kinnear
|
|
|
ok final service change
|
Permanent Service | 8/14/2007 | 8/15/2007 | 8/15/2007 | A | PASS |
Mike Kinnear
|
|
|
Brian; Phone #: ###-#### Internet Inspection Request from: Hattie James p/s u/g reconnect ok
|
Final | 8/14/2007 | 8/14/2007 | 8/14/2007 | P | FAIL |
Mike Kinnear
|
|
|
Brian, please call 1st for access; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt no service bonding to water system & service needs grounding choke for grounding electrode. note wrong type inspection should have been for per. service.
|