Permit Information
Permit NumberELE07-02794
StatusFinaled
Name DAVIS ELECTRICAL CONTRACTORS
Site Address 3514 W GREENBRIER DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/7/20081/7/20081/7/2008PPASS
DetailsBob Reichert
mike Phone #: ###-#### ok to final
Electrical Rough-In10/3/200710/4/200710/4/2007APASS
DetailsBob Reichert
craig Phone #: ###-#### called contr, needs some nailplates, close openings in panel, ric ok main floor only
Permanent Service10/4/200710/4/200710/4/2007PPASS
DetailsBob Reichert
craig Phone #: ###-#### corrections made, p/s o/h rec ok
Permanent Service8/10/20078/10/20078/10/2007PFAIL
DetailsBob Reichert
###-#### mike called, left message, left corr notice, nec 250.24(A) gec shall connect to grounded service conductor at service, 250.52(A)(1) shall connect to water pipe within 5' of entering building,250.53(D)(2) shall supplement water pipe with ground rods, 404.8 center of operating handle of breaker shall not be over 6'-7" above floor, 230.24(A) service drop conductors shall be 8' above roof