Final | 8/24/2007 | 8/24/2007 | 8/24/2007 | P | PASS |
Jack Frank
|
|
|
Pat Gill or Roger Reynolds ###-#### as contacts Phone #: ###-#### Internet Inspection Request from: Debby Ellis ok corrections made card signed
|
Final | 8/23/2007 | 8/23/2007 | 8/23/2007 | P | FAIL |
Jack Frank
|
|
|
Pat Gill contact or Roger Reynolds ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis see added r/i
|
Electrical Rough-In | 8/23/2007 | 8/23/2007 | 8/23/2007 | P | FAIL |
Jack Frank
|
|
|
Pat Gill contact or Roger Reynolds ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis corr, 400.8(5) no cords allowed above ceilings, all for exam rm shall meet 517.13 a&b no flex for branch circuits feeding exam rm
|