Final | 1/17/2008 | 1/18/2008 | 1/18/2008 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham corrections made, ok to final
|
Final | 1/17/2008 | 1/17/2008 | 1/17/2008 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham called, left correction notice, nec 352.30(A) rnc shall be supported within 3' of conduit termination, 404.9(A) switch faceplate shall seat against finished surface- upper bath, 406.4(E) receptacles shall not be installed in a face up position, 406.8(D) floor receptacles shall allow floor cleaning equipment to be operated without damage to the receptacle, 110.3(B) listed or labelled equipment shall be installed in accordance with instructions- jetted tub
|
Final | 1/16/2008 | 1/18/2008 | 1/17/2008 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham Inspection cancelled from web by: Brandon Blackham
|
Final | 1/16/2008 | 1/16/2008 | 1/16/2008 | P | CANC |
Bob Reichert
|
|
|
branon Phone #: ###-#### called contractor, left message, floor finisher would not allow traffic on floors, told to recall
|
Rough-In Permanent Service | 8/29/2007 | 8/29/2007 | 8/29/2007 | P | PASS |
William E Thomas
|
|
|
brandon Phone #: ###-#### 1. ri ok . 2. p/s u/g n ok .
|