Final | 9/7/2007 | 9/7/2007 | 9/7/2007 | P | PASS |
Jim Schmer
|
|
|
temp power pole Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA t/s o/h new ok jms
|
Temporary Service | 9/4/2007 | 9/4/2007 | 9/4/2007 | P | FAIL |
Bob Reichert
|
|
|
todd Phone #: ###-#### called, nec 250.53(G) electrode shall be flush with ground, 230.23(B)(4) minimum clearance shall be 18 ft above grade in alley, 230.2 shall supply building with only 1 service, BCC shall provide min 120 and 250 volt recpts with gfci protection
|