Final | 9/20/2007 | 9/20/2007 | 9/20/2007 | P | PASS |
Bob Reichert
|
|
|
mike Phone #: ###-#### ok to final
|
Rough-In Permanent Service | 9/12/2007 | 9/12/2007 | 9/12/2007 | P | PASS |
Bob Reichert
|
|
|
mike Phone #: ###-#### corr made, p/s o/h n ok
|
Rough-In Permanent Service | 9/4/2007 | 9/4/2007 | 9/4/2007 | P | FAIL |
Bob Reichert
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Hattie James called, nec 312.5 shall provide abrasion protection for all conductors entering enclosure, 550.32(B) shall meet all criteria for this part of article ( mfgrs instruction to allow service on structure) 250.52(A)(3) concrete encased electrode sahll be provided
|