Final | 10/29/2007 | 10/29/2007 | 10/29/2007 | P | PASS |
Jack Frank
|
|
|
jr Phone #: ###-#### ok
|
Electrical Rough-In | 9/13/2007 | 9/13/2007 | 9/13/2007 | P | PASS |
Jack Frank
|
|
|
J R; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok
|
Electrical Rough-In | 9/11/2007 | 9/12/2007 | 9/12/2007 | A | FAIL |
Jack Frank
|
|
|
CHRIS Phone #: ###-#### corrections not made called
|
Electrical Rough-In | 9/4/2007 | 9/5/2007 | 9/5/2007 | P | FAIL |
Jack Frank
|
|
|
CHRIS Phone #: ###-#### 210.11(C)(2)&(3) needs laundry circuit, outside outlet not allowed on bath circuit, 300.4(A)(1) nail plates inside outside edges, 314.16 box fill, 314.20 outside boxes not flush, 110.3(B) use manufactures breakers only, BCC no violations retained wiring of addition shall meet NEC for new dwelling 220 shall provide service calcs called corr do not cover posted also reinspection fee due COW
|