Final | 12/20/2007 | 12/21/2007 | 12/21/2007 | A | PASS |
Bob Reichert
|
|
|
We have made the nessary corrections Phone #: ###-#### Internet Inspection Request from: Scott Abbott corrections made, signed occupancy card, ok to final
|
Final | 12/19/2007 | 12/20/2007 | 12/20/2007 | A | PART |
Bob Reichert
|
|
|
We are ready for our final Phone #: ###-#### Internet Inspection Request from: Scott Abbott met electrician,left correction notice, BCC there shall be no nm cable installed in commercial, retail electrical installations, address shall be posted, signed t/o card
|
Final | 12/17/2007 | 12/17/2007 | 12/17/2007 | P | NR |
Jack Frank
|
|
|
All we have left is the point of sale they would like to move in merchindise this week so could you please do a final on all but point of sale Phone #: ###-#### Internet Inspection Request from: Scott Abbott talked with contr job not ready also needs listed fan boxes for paddle fans
|
Electrical Rough-In | 11/19/2007 | 11/19/2007 | 11/19/2007 | P | PART |
Jack Frank
|
|
|
we are ready for the cieling to be inspected for cover Phone #: ###-#### Internet Inspection Request from: Scott Abbott ceilings ok damaged panel removed, note needs show window outlets reinstalled
|
Electrical Rough-In | 10/11/2007 | 10/11/2007 | 10/11/2007 | P | FAIL |
Bob Reichert
|
|
|
ceiling and panel Phone #: ###-#### Internet Inspection Request from: Scott Abbott talked with contr, left correction notice to owner and elect. BCC no violations shall be retained, all ceiling tiles shall be removed for inspection, address shall be posted, NEC 110.12(C) there shall be no damaged parts that may adversely affect safe operation of equipment
|
Electrical Rough-In | 10/8/2007 | 10/9/2007 | 10/9/2007 | A | PASS |
Bob Reichert
|
|
|
We have opened up the floor and reinstlalled underground it is ready to be inspected thanks Scott Phone #: ###-#### Internet Inspection Request from: Scott Abbott correction made, u/g ok to cover
|
Electrical Rough-In | 10/4/2007 | 10/5/2007 | 10/5/2007 | A | PART |
Bob Reichert
|
|
|
we have made the correction with the exception of the covered floor box Dave will be on the job site to go over what can be done about this issue Phone #: ###-#### Internet Inspection Request from: Scott Abbott ric ok walls and hard lids only, they will dig up u/g to 2 floor boxes only, single appears to be deep enough and call for inspection
|
Electrical Rough-In | 10/3/2007 | 10/4/2007 | 10/4/2007 | A | FAIL |
Bob Reichert
|
|
|
The wall only for dry wall cover Phone #: ###-#### Internet Inspection Request from: Scott Abbott called, left correction notice,nec 330.30(B) mc cable shall be secured within 12" of box, 250.80 metal enclosures shall be grounded, 110.12(A) unused openings shall be closed in boxes,BCC all make-up shall be done, all underground shall be inspected before cover
|