Final | 1/2/2008 | 1/2/2008 | 1/2/2008 | A | PASS |
Bob Reichert
|
|
|
see ri on 12-27-07, ok to final
|
Electrical Rough-In | 12/26/2007 | 12/27/2007 | 12/27/2007 | A | PASS |
Bob Reichert
|
|
|
mark Note: 1st thing is possible Phone #: ###-#### corrections made, ok to final
|
Final | 12/24/2007 | 12/26/2007 | 12/26/2007 | A | FAIL |
Bob Reichert
|
|
|
dean Phone #: ###-#### corrections not all made, see list on correction notice
|
Final | 12/21/2007 | 12/24/2007 | 12/24/2007 | A | FAIL |
Bob Reichert
|
|
|
dean Phone #: ###-#### met owner, left corr notice, nec 334.15(B) nm cable shall be protected from physical damage with raceway, 422.30 shall provide disconnect for furnace, 404.9 faceplates for switches shall completely cover opening and seat against finished surface, 406.4 recpts shall be securely mounted in place, 406.4(D) receptacle faces shall be flush with or project from faceplates, 406.5 recpt faceplates shall completely cover opening and seat against mounting surface, 408.4 circuit directory shall be clear, concise, and evident for specific circuits,210.8 kitchen recpts shall be gfci protected-min 2 circuits, 210.12 bedrooms shall be protected by afci, 250.50 grounding electrode (water pipe) shall be used as grounding electrode,BCC all wiring shall be done and protected-range hood
|
Electrical Rough-In | 11/23/2007 | 11/26/2007 | 11/26/2007 | P | PASS |
Bob Reichert
|
|
|
Dean Phone #: ###-#### corrections made, ric ok
|
Electrical Rough-In | 11/21/2007 | 11/21/2007 | 11/21/2007 | P | NR |
Bob Reichert
|
|
|
Dean Phone #: ###-#### still working on corrections, told owner they had to have all work done and corrections made before release for cover, also told that they are about to lose their permit
|
Electrical Rough-In | 11/15/2007 | 11/15/2007 | 11/15/2007 | P | FAIL |
Bob Reichert
|
|
|
chewey Phone #: ###-#### met owner, reviewed following: left correction notice,NEC 110.11 there shall be no agents that will deteriorate conductors, 250.86 shall ground metal boxes with approved means, 300.14 shall provide 6" free conductor length in boxes, 110.12(C) there shall be no broken boxes, 210.52(A)(1) no point along floor line shall be over 6' from a receptacle, 210.52(A)(2) wall space is 2' along floor line and shall have receptacle installed, 314.17(C) nm cable shall be stapled within 8" of 2x4 box, 210.12(B) bedrooms shall have listed arc fault circuit interrupters installed, 210.52(C)(1) countertops shall have receptacles installed within 2' of sink edge
|
Permanent Service | 11/6/2007 | 11/7/2007 | 11/7/2007 | A | PASS |
Bob Reichert
|
|
|
mark Phone #: ###-#### p/s u/g rec ok
|
Rough-In Permanent Service | 11/5/2007 | 11/6/2007 | 11/6/2007 | A | CANC |
Bob Reichert
|
|
|
mark Phone #: ###-#### see conference
|
Conference | 11/6/2007 | 11/6/2007 | 11/6/2007 | P | DONE |
Bob Reichert
|
|
|
mark Phone #: ###-#### met brother and reviewed stapling, panel height, 1 1/4",ground rods, ground screws, no screws in boxes, staple romex flat, 6" free conductor, outlet spacing
|
Electrical Rough-In | 11/5/2007 | 11/5/2007 | 11/5/2007 | P | NR |
Mike Kinnear
|
|
|
mark - please call 1/2 hr prior to inspection Phone #: ###-#### conf with mark regarding ri & service -- wall spacing, 1 1/4 stapling, free length of conducters. 8inch & 12inch support. needs romex connector for ser cable leaving service box.
|
Conference | 9/19/2007 | 9/20/2007 | 9/20/2007 | A | DONE |
Bob Reichert
|
|
|
Mark ###-#### talked about service and sub-panel, code requirements for new part of construction, not bringing existing up to code, using old conductors, using gfci ahead of 2-wire recpts
|