Final | 11/9/2007 | 11/9/2007 | 11/9/2007 | A | PASS |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman
|
Final | 11/7/2007 | 11/7/2007 | 11/7/2007 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman corr called BCC &410.8 correct type fixtures and clearence closet , 334.15 protect romex in island also box fill 314.16
|
Permanent Service | 9/24/2007 | 9/24/2007 | 9/24/2007 | A | PASS |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman P/S O/H R OK
|
Rough-In Permanent Service | 9/21/2007 | 9/21/2007 | 9/21/2007 | P | PART |
Pat Lass
|
|
|
we should be ready around 12:00. Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman R/I Ok service has undersized J box 250.148 all grounds tied together and to the box
|