Final | 1/11/2008 | 1/11/2008 | 1/11/2008 | P | PASS |
Jack Frank
|
|
|
Access code garage 22080 Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok survey called 410.8
|
Rough-In Permanent Service | 9/21/2007 | 9/21/2007 | 9/21/2007 | P | PASS |
William E Thomas
|
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas . 1. ri ok. . . 2. ri p/s u/g new ok
|
Rough-In Permanent Service | 9/19/2007 | 9/20/2007 | 9/20/2007 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas corr called300.4 needs nail plates everywhere, 314.17(A&C) replace outside recept boxes with broken out factory clamps, 334.23 protect cables within 6ft of attic accesses, BCC complete all makeup and grd boxes (outside lights and recepts)
|