Final | 3/6/2008 | 3/6/2008 | 3/6/2008 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/6/2008 at 10:44:04 AM. Contact: ###-####. corrections made, ok to final
|
Final | 3/4/2008 | 3/5/2008 | 3/5/2008 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/4/2008 at 12:44:45 PM. Contact: ###-####. called contractor, left correction notice, NEC 406.4(D) receptacles faces shall be flush with or project from faceplates,404.4 switches shall not be installed in tub area, 348.30(A) fmc shall be fastened within 12" of box, 300.10 shall securely fasten raceway fitting to box, 400.8 shall not use flexible cord in lieu of permanent wiring, BCC shall provide globe guard for undercounter fixture, shall provide listing for control box for pump controller
|
Rough-In Permanent Service | 9/27/2007 | 9/28/2007 | 9/28/2007 | A | PASS |
Pat Lass
|
|
|
John; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt P/S O/H N Ok R/I OK
|