Final | 10/22/2007 | 10/23/2007 | 10/23/2007 | A | PASS |
Jack Frank
|
|
|
george Note: also attic Phone #: ###-#### ok card signed
|
Electrical Rough-In | 10/23/2007 | 10/23/2007 | 10/23/2007 | A | PASS |
Jack Frank
|
|
|
george Note: also attic Phone #: ###-#### ceiling ok called needs 2 1/2" KOs
|
Electrical Rough-In | 10/2/2007 | 10/3/2007 | 10/3/2007 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/2/2007 at 8:35:13 PM. Contact: ###-####. walls only ok to cover, corrections made
|
Electrical Rough-In | 10/1/2007 | 10/2/2007 | 10/2/2007 | A | FAIL |
Bob Reichert
|
|
|
george Phone #: ###-#### called, left corr notice, nec 300.4(A) & (D) edge of bored holes, mc cable and ent shall be 1 1/4" from edge of framing members, BCC raceways shall not be run in valley of framing members
|