Final | 11/28/2007 | 11/28/2007 | 11/28/2007 | P | PASS |
Mike Kinnear
|
|
|
Contact is Jay Sprik. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok final
|
Final | 11/27/2007 | 11/28/2007 | 11/28/2007 | A | NR |
Mike Kinnear
|
|
|
jay Phone #: ###-#### arcfault will not reset & no furnace disconnect
|
Permanent Service | 10/8/2007 | 10/8/2007 | 10/8/2007 | P | PASS |
Pat Lass
|
|
|
jay Phone #: ###-#### check distance between ground rods on final P/S O/h R Ok
|
Rough-In Permanent Service | 10/8/2007 | 10/8/2007 | 10/8/2007 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 10/8/2007 at 6:55:44 AM. Contact: ###-####. service not ready ground rods too close together, water ground not connected, mast has no support and telepnone is attached to it.
|
Electrical Rough-In | 10/5/2007 | 10/8/2007 | 10/8/2007 | A | CANC |
Pat Lass
|
|
|
Re-inspect. Contact is Jay Sprik. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery Disp set to [CANC] by a contractor via Hello! on Oct 8 2007 7:04AM.
|
Electrical Rough-In | 10/5/2007 | 10/5/2007 | 10/5/2007 | P | FAIL |
William E Thomas
|
|
|
andy Phone #: ###-#### . 1. 300.4-- 1 1/4" protection both bored holes and parallel to framing members.
|
Electrical Rough-In | 10/3/2007 | 10/4/2007 | 10/4/2007 | P | CANC |
Mike Kinnear
|
|
|
Removed and replaced old panel, did not upsize. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery Inspection cancelled from web by: Richard Montgomery
|
Electrical Rough-In | 10/4/2007 | 10/5/2007 | 10/4/2007 | A | CANC |
Mike Kinnear
|
|
|
Removed and replaced old panel, did not upsize. Contact is Jay Sprik. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery\\requires a building permit.
|