Permit Information
Permit NumberELE07-03432
StatusFinaled
Name ACE ELECTRIC AND CONTROL
Site Address 11818 W JOPLIN RD
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: grounding for new digestor 3 structure; per Monte w/ Ace Elec. increase scope of work to include new digester 3 control building, biofilter structrure and misc. digestor upgrades, new total cert of value is $637,830//3/12/08 LEG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/1/20094/1/20094/1/2009APASS
DetailsJack Frank
The Stahlin Fiberglass boxes recommend grounding hubs installed, we changed all of them, the non metallic Hoffman enclosure has markings in the box that call for ground bushings for metallic entries Phone #: ###-#### Internet Inspection Request from: Monty Adkinson ok looks like all violations corrected
Final3/30/20093/30/20093/30/2009PFAIL
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Monty Adkinson called corrections not made
Final3/25/20093/25/20093/25/2009PFAIL
DetailsJack Frank
Please call 1/2 hour ahead if possible, and I can have someone there if you would like. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson corr called left message, 250.97 shall provide bong for over 250 volts where box or enclosure is not listed to UL 514(A) and cocentric, eccentric KOs ane encountered, 110.3(B) and 314.3 follow manufactures instructions, if metal raceways are allowed and bond bushings, in all non-metallic boxes and enclosures,etc, 110.14(A) shall provide a good connections where stranded wire is use under grd screws, 344.46&342.46 shall provide bushing all locations where RMC,IMC is used
ELE-Aging Inspection2/9/20092/9/20092/9/2009 CANC
DetailsJack Frank
Electrical Rough-In2/9/20092/9/20092/9/2009APART
DetailsJack Frank
wsuc
Electrical Rough-In12/8/200812/9/200812/9/2008APART
DetailsJack Frank
Need inspection for digester 3 lid, utilidor C, biofilter area, filtrate area, blend tank area. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson ok also control rm ok
ELE-Aging Inspection10/29/200810/29/200810/29/2008 PART
DetailsJack Frank
wsuc
ELE-Aging Inspection8/26/20088/26/20088/26/2008 PART
DetailsJack Frank
wsuc
ELE-Aging Inspection6/16/20086/16/20086/16/2008 PART
DetailsJack Frank
called w s u c
Electrical Rough-In4/16/20084/16/20084/16/2008APART
DetailsJack Frank
Digester 3 concrete lid, cover inspection of Rigid pvc coated conduit in lid Phone #: ###-#### Internet Inspection Request from: Monty Adkinson ok
Electrical Rough-In2/12/20082/13/20082/13/2008APART
DetailsJack Frank
Need cover inspection conduits to be encased in concrete with in digester walls, north west section of digester Phone #: ###-#### Internet Inspection Request from:
Monty Adkinson vertical conduits in wall ok
ELE-Aging Inspection1/31/20081/31/20082/4/2008 PART
DetailsJack Frank
wsuc
Electrical Rough-In10/25/200710/25/200710/25/2007APART
DetailsJack Frank
Need cover inspection on main floor pad of new digester control building, located on PSI site. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson ok conduit in floor slab
Electrical Rough-In10/4/200710/5/200710/5/2007APART
DetailsJack Frank
please call to meet on site. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson grd ring for new digester ok