Final | 4/1/2009 | 4/1/2009 | 4/1/2009 | A | PASS |
Jack Frank
|
|
|
The Stahlin Fiberglass boxes recommend grounding hubs installed, we changed all of them, the non metallic Hoffman enclosure has markings in the box that call for ground bushings for metallic entries Phone #: ###-#### Internet Inspection Request from: Monty Adkinson ok looks like all violations corrected
|
Final | 3/30/2009 | 3/30/2009 | 3/30/2009 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Monty Adkinson called corrections not made
|
Final | 3/25/2009 | 3/25/2009 | 3/25/2009 | P | FAIL |
Jack Frank
|
|
|
Please call 1/2 hour ahead if possible, and I can have someone there if you would like. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson corr called left message, 250.97 shall provide bong for over 250 volts where box or enclosure is not listed to UL 514(A) and cocentric, eccentric KOs ane encountered, 110.3(B) and 314.3 follow manufactures instructions, if metal raceways are allowed and bond bushings, in all non-metallic boxes and enclosures,etc, 110.14(A) shall provide a good connections where stranded wire is use under grd screws, 344.46&342.46 shall provide bushing all locations where RMC,IMC is used
|
ELE-Aging Inspection | 2/9/2009 | 2/9/2009 | 2/9/2009 | | CANC |
Jack Frank
|
|
|
|
Electrical Rough-In | 2/9/2009 | 2/9/2009 | 2/9/2009 | A | PART |
Jack Frank
|
|
|
wsuc
|
Electrical Rough-In | 12/8/2008 | 12/9/2008 | 12/9/2008 | A | PART |
Jack Frank
|
|
|
Need inspection for digester 3 lid, utilidor C, biofilter area, filtrate area, blend tank area. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson ok also control rm ok
|
ELE-Aging Inspection | 10/29/2008 | 10/29/2008 | 10/29/2008 | | PART |
Jack Frank
|
|
|
wsuc
|
ELE-Aging Inspection | 8/26/2008 | 8/26/2008 | 8/26/2008 | | PART |
Jack Frank
|
|
|
wsuc
|
ELE-Aging Inspection | 6/16/2008 | 6/16/2008 | 6/16/2008 | | PART |
Jack Frank
|
|
|
called w s u c
|
Electrical Rough-In | 4/16/2008 | 4/16/2008 | 4/16/2008 | A | PART |
Jack Frank
|
|
|
Digester 3 concrete lid, cover inspection of Rigid pvc coated conduit in lid Phone #: ###-#### Internet Inspection Request from: Monty Adkinson ok
|
Electrical Rough-In | 2/12/2008 | 2/13/2008 | 2/13/2008 | A | PART |
Jack Frank
|
|
|
Need cover inspection conduits to be encased in concrete with in digester walls, north west section of digester Phone #: ###-#### Internet Inspection Request from: Monty Adkinson vertical conduits in wall ok
|
ELE-Aging Inspection | 1/31/2008 | 1/31/2008 | 2/4/2008 | | PART |
Jack Frank
|
|
|
wsuc
|
Electrical Rough-In | 10/25/2007 | 10/25/2007 | 10/25/2007 | A | PART |
Jack Frank
|
|
|
Need cover inspection on main floor pad of new digester control building, located on PSI site. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson ok conduit in floor slab
|
Electrical Rough-In | 10/4/2007 | 10/5/2007 | 10/5/2007 | A | PART |
Jack Frank
|
|
|
please call to meet on site. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson grd ring for new digester ok
|