DOC - Permit Finaled | | | 5/27/2008 | | DONE |
Bob Reichert
|
|
|
Ok to doc_final per phone call with Bob Reichert///5-27-08 BAS
|
Temporary Service | 11/9/2007 | 11/9/2007 | 11/9/2007 | P | FAIL |
Bob Reichert
|
|
|
called contractor, not all corrections made, fee due, called power company, about shutting off power as this was energized without inspection, but contractor took care of the most hazardous items before inspection made.
|
Final | 10/30/2007 | 10/31/2007 | 10/31/2007 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called, left message, left correction notice, nec 110.12(A) unused openings shall be closed, 110.26(A)(1) shall clear workspace in front of panel, 312.5 all conductors entering enclosures shall have abrasion protection, 408.38 shall provide deadfront 408.4 shall provide circuit directory, 314.25 boxes shall have covers installed, 406.8(B) shall use in-use covers- installed, 110.3(B) listed equipment shall be installed per manufacturers instructions and operate correctly
|