Final | 1/5/2009 | 1/5/2009 | 1/5/2009 | P | PASS |
Bob Reichert
|
|
|
dustin Phone #: ###-#### corrections made, ok to final
|
Final | 11/20/2008 | 11/21/2008 | 11/21/2008 | A | FAIL |
Jack Frank
|
|
|
dustin Phone #: ###-#### Note: please call 1/2 hr prior to inspection corr called 410.8 needs totally enclosed fixture MB closet, 410.4 needs shower trim, 406.3 and BCC needs gfci all replace recepts in kit. for countertops, 406. 4&5 recepts shall tight in boxes and flush with plates
|
Conference | 5/13/2008 | 5/13/2008 | 5/13/2008 | P | DONE |
Bob Reichert
|
|
|
told contractor that permit would be ok to call for final when ready
|
Electrical Rough-In | 11/13/2007 | 11/14/2007 | 11/14/2007 | P | PASS |
Bob Reichert
|
|
|
DUSTIN NOTE: PLEASE CALL 1/2 HR TO MEET WITH Phone #: ###-#### ric ok
|
Electrical Rough-In | 11/13/2007 | 11/13/2007 | 11/13/2007 | P | NH |
Bob Reichert
|
|
|
Dustin at ###-####; call for access called 2x, left message said to recall when available
|
Permanent Service | 10/11/2007 | 10/12/2007 | 10/12/2007 | A | PASS |
Bob Reichert
|
|
|
dustin Phone #: ###-#### p/s o/h rec ok
|