Final | 12/4/2007 | 12/5/2007 | 12/5/2007 | P | PASS |
Bob Reichert
|
|
|
TOBY Phone #: ###-#### Internet Inspection Request from: Sean DeLacy corrections made, signed occ card, ok to final
|
Final | 12/3/2007 | 12/4/2007 | 12/4/2007 | P | FAIL |
Jack Frank
|
|
|
TOBY Phone #: ###-#### Internet Inspection Request from: Sean DeLacy not ready needs to bond hot and cold sized to T250.66 110.12(A) seal KOs in panels, 406.4&5 recepts loose and set back in plates, single duplex recept under counter at drive thru window bottom half does not test out right ? called
|
Electrical Rough-In | 11/28/2007 | 11/29/2007 | 11/29/2007 | P | PASS |
Mike Kinnear
|
|
|
TOBY CEILING COVER Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok cover ceiling & southeast corner conduit with concrete for ballard
|
Electrical Rough-In | 11/5/2007 | 11/6/2007 | 11/6/2007 | P | PASS |
Bob Reichert
|
|
|
TOBY CEILING COVER Phone #: ###-#### Internet Inspection Request from: Sean DeLacy hard lids only ok to cover
|
Electrical Rough-In | 11/1/2007 | 11/1/2007 | 11/1/2007 | P | PASS |
Bob Reichert
|
|
|
wall cover Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ric ok walls only
|
Electrical Rough-In | 10/25/2007 | 10/25/2007 | 10/25/2007 | P | PASS |
Bob Reichert
|
|
|
TOBY CALL PRIOR TO HEADING TO SITE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok to cover u/g
|
Electrical Rough-In | 10/25/2007 | 10/26/2007 | 10/25/2007 | A | CANC |
Bob Reichert
|
|
|
TOBY UNDERSLAB INSPECTION Phone #: ###-#### Internet Inspection Request from: Sean DeLacy Inspection cancelled from web by: Sean DeLacy
|