ELE-Aging Inspection | 2/2/2010 | 2/2/2010 | 2/8/2010 | | DONE |
Bob Reichert
|
|
|
no activity, see doc expire
|
DOC - Permit Expired | 2/8/2010 | 2/8/2010 | 2/8/2010 | A | PASS |
Bob Reichert
|
|
|
no activity, ok to doc expire
|
ELE-Aging Inspection | 12/2/2009 | 12/2/2009 | 12/4/2009 | | DONE |
Bob Reichert
|
|
|
no activity
|
Electrical Rough-In | 11/28/2007 | 11/28/2007 | 11/28/2007 | P | FAIL |
Mike Kinnear
|
|
|
linda - please call 1/2 hr prior to inspection Phone #: ###-#### home owner did not do the work she staed that she would get an electrical contractor to complete the job. note service change is incorrect needs two ground rods, ground water system, put grounding electrode conductor & grounded conductor on same bus bar, proper breakers for wire size, boxes for lights over bathrm vanity, & all grounding condutors in boxes shall tied together.
|
Conference | 11/1/2007 | 11/2/2007 | 11/2/2007 | A | DONE |
Bob Reichert
|
|
|
per mike kinner meet homeowner at 8- linda-- ###-#### work - or home ###-#### met owner and son-in-law, reviewed box fill, circuiting, listing for tub, 1 1/4" for holes and nm cable, nailplates, no nm stapled on edge, no screws in boxes to mount to framing members, ground for subpanel, ampacity for loads, whether or not listing allows #10 to be terminated on device, length of free conductor at box, water heater wiring, tub install wiring, make-up for ri inspection and when to call for inspection
|
Conference | 10/29/2007 | 10/30/2007 | 10/30/2007 | P | PART |
Mike Kinnear
|
|
|
Linda Mike -Please call 15 min before going out Phone #: ###-#### t/w linda her son inlaw did the work. told her set up a meeting with he & i for conf.
|