Final | 5/8/2008 | 5/9/2008 | 5/9/2008 | A | PASS |
William E Thomas
|
|
|
garage code 1905 Phone #: ###-#### Internet Inspection Request from: Therrin Robertson . .1. final ok. . .
|
Electrical Rough-In | 3/12/2008 | 3/12/2008 | 3/12/2008 | A | PASS |
Mike Kinnear
|
|
|
ok cover floor heat only
|
Electrical Rough-In | 10/31/2007 | 11/1/2007 | 11/1/2007 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson corrections made, ric ok
|
Final | 10/30/2007 | 10/30/2007 | 10/30/2007 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson wrong type inspection request
|
Electrical Rough-In | 10/30/2007 | 10/30/2007 | 10/30/2007 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called contractor, left correction notice, NEC 210.53 shall provide receptacles per wall space provisions of (A)-1,2,3 (dining room, kitchen,upstairs),300.4(D) nm cable shall be 1 1/4" from edge of framing members, BCC all make-up shall be done- boxes provided, jetted tub set
|
Permanent Service | 10/30/2007 | 10/30/2007 | 10/30/2007 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson p/s u/g n ok
|