ELE-Aging Inspection | 12/25/2009 | 12/25/2009 | 12/30/2009 | | CANC |
Jack Frank
|
|
|
|
DOC - Permit Expired | 12/30/2009 | 12/30/2009 | 12/30/2009 | A | PASS |
Jack Frank
|
|
|
no action for 2years
|
Electrical Rough-In | 11/6/2007 | 11/8/2007 | 11/8/2007 | A | FAIL |
Jack Frank
|
|
|
Mike McCarrel Electrician Homeowner Ann McCuistion ###-#### Phone #: ###-#### Internet Inspection Request from: Jim Burnette corr. called 314.3 metallic raceway allowed in plastic box, 300.4 nail plates garage, 408.4 panel schedule bo specific, 408.7 seal breaker KO, 225.31&36 exception shed needs disconnect
|