Final | 11/8/2007 | 11/8/2007 | 11/8/2007 | P | CANC |
Bob Reichert
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt see t/s
|
Temporary Service | 11/8/2007 | 11/8/2007 | 11/8/2007 | P | PASS |
Bob Reichert
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corrections made, t/s o/h n ok
|
Temporary Service | 11/7/2007 | 11/8/2007 | 11/8/2007 | A | FAIL |
Bob Reichert
|
|
|
mike Phone #: ###-#### called, left correction notice, nec 250.24(A) gec shall connect to grounded service conductor, 250.53(G) upper end of electrode shall be flush with or below ground level, 250.24(B) shall instasll main bonding jumper
|