Final | 2/6/2008 | 2/7/2008 | 2/7/2008 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/6/2008 at 11:15:53 PM. Contact: ###-####. ok to final, signed occupancy card, gave courtesty correction notice to change breakers back to 15A for signs
|
Electrical Rough-In | 12/12/2007 | 12/13/2007 | 12/13/2007 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 12/12/2007 at 10:22:36 PM. Contact: ###-####. met contractor, left correction notice for open ceiling in electrical room-nec 110.26(F)(1)(a)&(b) the space equal to the width and depth of the equipment to a height of 6' above the equipment shall be dedicated to the electrical installation. Shall install drip protection for foreign systems above dedicated space, ok to cover walls and hard lid ceilings
|