Permit Information
Permit NumberELE07-03759
StatusFinaled
Name ELCOR ELECTRIC
Site Address 2700 W AIRPORT WAY
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Addition: Electrical Work
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/17/200712/17/200712/17/2007PPASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok to final, signed occupancy card
Electrical Rough-In12/13/200712/13/200712/13/2007PPASS
DetailsBob Reichert
Reinspection. Ceiling Phone #: ###-#### Internet Inspection Request from: Ryan Christensen corrections made, ok to cover ceiling
Electrical Rough-In12/12/200712/13/200712/13/2007AFAIL
DetailsBob Reichert
inspection for ceiling cover Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called contractor, left correction notice, nec 300.11(A) raceways shall be securely fastened in place, support wires shall be secured at both ends, no cables or wiring shall be supported by grid or tiles, 348.30(A) fmc shall be supported within 12" of termination point
Electrical Rough-In11/28/200711/29/200711/29/2007APASS
DetailsMike Kinnear
Re-inspection Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok cover walls only meeting rm & hallway to new section.
Electrical Rough-In11/28/200711/28/200711/28/2007PCANC
DetailsBob Reichert
Re-inspection. the later afternoon if possible.

Thank you! Phone #: ###-#### Internet Inspection Request from: Ryan Christensen Inspection cancelled from web by: Ryan Christensen
Electrical Rough-In11/26/200711/27/200711/27/2007AFAIL
DetailsMike Kinnear
Interior Walls Phone #: ###-#### Internet Inspection Request from: Ryan Christensen nec300.4(A)(1) bored holes 1 1/4 inch edge of framing member 300.4(D) cable support 1 1/4 inch from both sides of framing member runnin parallel
Electrical Rough-In11/13/200711/13/200711/13/2007PPASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called contractor, new room east side ok to cover
Rough-In Permanent Service11/9/200711/9/200711/9/2007PCANC
DetailsBob Reichert
Re inspection for Rough in Phone #: ###-#### Internet Inspection Request from: Ryan Christensen wrong type inspection request, see ri
Electrical Rough-In11/9/200711/9/200711/9/2007PPART
DetailsBob Reichert
Re inspection for Rough in Phone #: ###-#### Internet Inspection Request from: Ryan Christensen corrections made, ok to cover walls only and to insulate ceiling only south side of exst office
Rough-In Permanent Service11/8/200711/8/200711/8/2007PFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen caleed, left correction notice, nec 330.30(B) mc cable shall be strapped within 12' of box, 258.30(A) emt shall be supported within 3' of box, 300.4(A)&(D) edge of bored holes and raceways shall be 1 1/4" from edge of framing members