Final | 12/17/2007 | 12/17/2007 | 12/17/2007 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok to final, signed occupancy card
|
Electrical Rough-In | 12/13/2007 | 12/13/2007 | 12/13/2007 | P | PASS |
Bob Reichert
|
|
|
Reinspection. Ceiling Phone #: ###-#### Internet Inspection Request from: Ryan Christensen corrections made, ok to cover ceiling
|
Electrical Rough-In | 12/12/2007 | 12/13/2007 | 12/13/2007 | A | FAIL |
Bob Reichert
|
|
|
inspection for ceiling cover Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called contractor, left correction notice, nec 300.11(A) raceways shall be securely fastened in place, support wires shall be secured at both ends, no cables or wiring shall be supported by grid or tiles, 348.30(A) fmc shall be supported within 12" of termination point
|
Electrical Rough-In | 11/28/2007 | 11/29/2007 | 11/29/2007 | A | PASS |
Mike Kinnear
|
|
|
Re-inspection Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok cover walls only meeting rm & hallway to new section.
|
Electrical Rough-In | 11/28/2007 | 11/28/2007 | 11/28/2007 | P | CANC |
Bob Reichert
|
|
|
Re-inspection. the later afternoon if possible.
Thank you! Phone #: ###-#### Internet Inspection Request from: Ryan Christensen Inspection cancelled from web by: Ryan Christensen
|
Electrical Rough-In | 11/26/2007 | 11/27/2007 | 11/27/2007 | A | FAIL |
Mike Kinnear
|
|
|
Interior Walls Phone #: ###-#### Internet Inspection Request from: Ryan Christensen nec300.4(A)(1) bored holes 1 1/4 inch edge of framing member 300.4(D) cable support 1 1/4 inch from both sides of framing member runnin parallel
|
Electrical Rough-In | 11/13/2007 | 11/13/2007 | 11/13/2007 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called contractor, new room east side ok to cover
|
Rough-In Permanent Service | 11/9/2007 | 11/9/2007 | 11/9/2007 | P | CANC |
Bob Reichert
|
|
|
Re inspection for Rough in Phone #: ###-#### Internet Inspection Request from: Ryan Christensen wrong type inspection request, see ri
|
Electrical Rough-In | 11/9/2007 | 11/9/2007 | 11/9/2007 | P | PART |
Bob Reichert
|
|
|
Re inspection for Rough in Phone #: ###-#### Internet Inspection Request from: Ryan Christensen corrections made, ok to cover walls only and to insulate ceiling only south side of exst office
|
Rough-In Permanent Service | 11/8/2007 | 11/8/2007 | 11/8/2007 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen caleed, left correction notice, nec 330.30(B) mc cable shall be strapped within 12' of box, 258.30(A) emt shall be supported within 3' of box, 300.4(A)&(D) edge of bored holes and raceways shall be 1 1/4" from edge of framing members
|