Final | 3/31/2008 | 4/1/2008 | 4/1/2008 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Alan Lusk corrections made, ok to final
|
Final | 3/26/2008 | 3/27/2008 | 3/27/2008 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Alan Lusk met contractor, left correction notice, NEC 110.26 shall maintain work space about equipment, 408.4 shall complete circuit directory, 210.52(E) shall provide receptacle at front of dwelling, 406.4 receptacles shall be securely fastened in place
|
Rough-In Permanent Service | 11/8/2007 | 11/9/2007 | 11/9/2007 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Alan Lusk met elect, ric ok, p/s u/g n ok
|