Final | 6/24/2008 | 6/24/2008 | 6/24/2008 | P | PASS |
William E Thomas
|
|
|
Jeremy Phone #: ###-#### final ok
|
Rough-In Permanent Service | 1/2/2008 | 1/2/2008 | 1/2/2008 | P | PASS |
Bob Reichert
|
|
|
call 1/2 prior-- jason Phone #: ###-#### corrections made, ric ok, NOTE: no underground house to garage done. p/s o/h n ok
|
Rough-In Permanent Service | 12/28/2007 | 12/28/2007 | 12/28/2007 | P | FAIL |
Bob Reichert
|
|
|
jeremey ###-#### called, left message, left corr notice,nec 404.8 center grip of breaker handle at service shall not be over 6'-7" above grade, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 314.17(C) nm cable shall be stapled within 8" of box, 408.7 unused breaker openings shall be closed, BCC all make-up shall be done including boxes- out back, kitchen, and boxes shall have wiring installed, no u/g to garage seen or done, disconnects for garage service not done
|