Permit Information
Permit NumberELE07-03888
StatusFinaled
Name RONALD HOLDEN
Site Address 2918 N ESQUIRE DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/11/20081/14/20081/14/2008APASS
DetailsBob Reichert
Ron, call 20 minutes prior; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corrections made, ok to final
Final1/11/20081/11/20081/11/2008PFAIL
DetailsBob Reichert
ron - please call 1/2 hr prior to inspection Phone #: ###-#### met owner, nec corrections 210.8(A)(2) receptacles shall be gfci protected, 408.4 circuit directory shall be correct, 314.25 completed installations require box to be covered, 406.5 shall install receptacle faceplates
Electrical Rough-In12/10/200712/10/200712/10/2007PPASS
DetailsWilliam E Thomas
Ron holden Please call 20 min before going out Phone #: ###-####
. 1. ri ok.
Electrical Rough-In11/30/200712/3/200712/3/2007AFAIL
DetailsJack Frank
Please call at least 20 mins prior to inspection-Ron holden Phone #: ###-####
300.4 nail plates and 11/4", 110.3(B) p/s at shop needs main breaker, 314.23 &B C C no cutin boxes for new construction, needs conn for GEC, B C C complete all makeup, 314.3 needs bond bushing metal raceway in plastic jbox at house, 352.12(C) needs schedule 80 for exposed sections of PVC, grd to concrete encased electrode
Conference11/19/200711/20/200711/20/2007ADONE
DetailsBob Reichert
Ronald Please call 15 min before so he can meet you at the job. Phone #: ###-#### talked about service to shop. grounding for concrete encased electrode, make-up, 1 1/4", when to call for inspection