Final | 1/11/2008 | 1/14/2008 | 1/14/2008 | A | PASS |
Bob Reichert
|
|
|
Ron, call 20 minutes prior; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corrections made, ok to final
|
Final | 1/11/2008 | 1/11/2008 | 1/11/2008 | P | FAIL |
Bob Reichert
|
|
|
ron - please call 1/2 hr prior to inspection Phone #: ###-#### met owner, nec corrections 210.8(A)(2) receptacles shall be gfci protected, 408.4 circuit directory shall be correct, 314.25 completed installations require box to be covered, 406.5 shall install receptacle faceplates
|
Electrical Rough-In | 12/10/2007 | 12/10/2007 | 12/10/2007 | P | PASS |
William E Thomas
|
|
|
Ron holden Please call 20 min before going out Phone #: ###-#### . 1. ri ok.
|
Electrical Rough-In | 11/30/2007 | 12/3/2007 | 12/3/2007 | A | FAIL |
Jack Frank
|
|
|
Please call at least 20 mins prior to inspection-Ron holden Phone #: ###-#### 300.4 nail plates and 11/4", 110.3(B) p/s at shop needs main breaker, 314.23 &B C C no cutin boxes for new construction, needs conn for GEC, B C C complete all makeup, 314.3 needs bond bushing metal raceway in plastic jbox at house, 352.12(C) needs schedule 80 for exposed sections of PVC, grd to concrete encased electrode
|
Conference | 11/19/2007 | 11/20/2007 | 11/20/2007 | A | DONE |
Bob Reichert
|
|
|
Ronald Please call 15 min before so he can meet you at the job. Phone #: ###-#### talked about service to shop. grounding for concrete encased electrode, make-up, 1 1/4", when to call for inspection
|