ELE-Aging Inspection | 2/18/2008 | 2/18/2008 | 2/20/2008 | | DONE |
Jack Frank
|
|
|
|
Final | 2/20/2008 | 2/20/2008 | 2/20/2008 | A | PASS |
Jack Frank
|
|
|
|
Electrical Rough-In | 11/28/2007 | 11/28/2007 | 11/28/2007 | P | PASS |
Jack Frank
|
|
|
Guy Phone #: ###-#### p/s u/g new ok
|
Permanent Service | 11/26/2007 | 11/27/2007 | 11/27/2007 | P | FAIL |
Jack Frank
|
|
|
guy Phone #: ###-#### corr. not made more created called
|
Electrical Rough-In | 11/23/2007 | 11/26/2007 | 11/26/2007 | A | FAIL |
Jack Frank
|
|
|
reinspect; Guy Phone #: ###-#### corr. called 250.92 needs bonding at nipple between meter and sevice, T310.16 needs 4/0 cu. or 250 KCmil
|
Permanent Service | 11/20/2007 | 11/23/2007 | 11/23/2007 | A | NH |
Pat Lass
|
|
|
guy Phone #: ###-#### no access
|