Permit Information
Permit NumberELE07-03907
StatusFinaled
Name RUNDLE ELECTRIC
Site Address 7503 W NORTHVIEW CIR
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Addition: All electrical for addition to school.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/1/20084/2/20084/2/2008APASS
DetailsJack Frank
St. Mark''s School Addition Final. Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok card signed
Final3/31/20083/31/20083/31/2008PFAIL
DetailsJack Frank
St. Mark''s School Addition Final. Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery nr and violations met with contr explained code requirements to correct violations
Permanent Service3/26/20083/26/20083/26/2008PPASS
DetailsJack Frank
Contact is Brian Cornell. Re-address issues from earlier inspection. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery p/s u/g new ok
Permanent Service3/25/20083/26/20083/26/2008AFAIL
DetailsJack Frank
Contact is Brian Cornell. St. Mark''s School Addition project. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery met contr all GEC shall terminate at service not subpanel, 250.122 (F)(1) shall provide 1/0 cu, or 3/0 al equip grds to subpanel old building, 250.70 grd clamps shall be listed for proper size conductor, 250.64(E) shall use listed metallic conn. or plastic for GEC at enclosures
Permanent Service3/25/20083/25/20083/25/2008PCANC
DetailsJack Frank
Contact is Brian Cornell. This is the permanent service inspection for the St. Mark''s School Addition project. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery contr called and canceled
Electrical Rough-In2/28/20082/29/20082/29/2008APART
DetailsJack Frank
Ceiling inspection. St. Mark''s School Addition. Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok
Electrical Rough-In1/28/20081/28/20081/28/2008PPART
DetailsJack Frank
Contact is Brian Cornell. St. Mark''s School Addition. We would like to be onsite at time of inspection. Please call us, maybe 30-60 minutes before your arrival and we will head to the site. Brian=###-#### or Jay ###-####. Thank you. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery r/i walls and hard ceilings new class rooms
Conference1/28/20081/28/20081/28/2008PDONE
DetailsJack Frank
Contact is Brian Cornell. St. Mark''s School Addition. We would like to be onsite at time of inspection. Please call us, maybe 30-60 minutes before your arrival and we will head to the site. Brian=###-#### or Jay ###-####. Thank you. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery conference on new p/s refeeding old p/s that will become sub gear, and outside feeder and grding to seperate building
Electrical Rough-In12/7/200712/7/200712/7/2007PPART
DetailsMike Kinnear
Contact is Brian Cornell. This inspection is to inspect the 2-in conduit underground panel feeds on the West side of the building before we bury them. Call Brian with any questions. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok cover part under ground conduit from building to transformer about 40ft to transformer from building. 6ft from building is to be covered with concrete.
Temporary Service12/3/200712/3/200712/3/2007AFAIL
DetailsJack Frank
Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery called needs seperate permit for t/s
Temporary Service11/29/200711/29/200711/29/2007PFAIL
DetailsMike Kinnear
Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery no grounding electrode --- grounding & grounded conductors need to be terminated on the same bus bar note reinspection fee for no grounding electrode.
Temporary Service11/28/200711/29/200711/28/2007ACANC
DetailsJack Frank
Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery Inspection cancelled from web by: Richard Montgomery
Rough-In Permanent Service11/21/200711/21/200711/21/2007PPART
DetailsJack Frank
Contact is Brian Cornell. This is to inspect the conduit for the service prior to burying the conduit. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok