Final | 4/1/2008 | 4/2/2008 | 4/2/2008 | A | PASS |
Jack Frank
|
|
|
St. Mark''s School Addition Final. Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok card signed
|
Final | 3/31/2008 | 3/31/2008 | 3/31/2008 | P | FAIL |
Jack Frank
|
|
|
St. Mark''s School Addition Final. Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery nr and violations met with contr explained code requirements to correct violations
|
Permanent Service | 3/26/2008 | 3/26/2008 | 3/26/2008 | P | PASS |
Jack Frank
|
|
|
Contact is Brian Cornell. Re-address issues from earlier inspection. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery p/s u/g new ok
|
Permanent Service | 3/25/2008 | 3/26/2008 | 3/26/2008 | A | FAIL |
Jack Frank
|
|
|
Contact is Brian Cornell. St. Mark''s School Addition project. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery met contr all GEC shall terminate at service not subpanel, 250.122 (F)(1) shall provide 1/0 cu, or 3/0 al equip grds to subpanel old building, 250.70 grd clamps shall be listed for proper size conductor, 250.64(E) shall use listed metallic conn. or plastic for GEC at enclosures
|
Permanent Service | 3/25/2008 | 3/25/2008 | 3/25/2008 | P | CANC |
Jack Frank
|
|
|
Contact is Brian Cornell. This is the permanent service inspection for the St. Mark''s School Addition project. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery contr called and canceled
|
Electrical Rough-In | 2/28/2008 | 2/29/2008 | 2/29/2008 | A | PART |
Jack Frank
|
|
|
Ceiling inspection. St. Mark''s School Addition. Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok
|
Electrical Rough-In | 1/28/2008 | 1/28/2008 | 1/28/2008 | P | PART |
Jack Frank
|
|
|
Contact is Brian Cornell. St. Mark''s School Addition. We would like to be onsite at time of inspection. Please call us, maybe 30-60 minutes before your arrival and we will head to the site. Brian=###-#### or Jay ###-####. Thank you. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery r/i walls and hard ceilings new class rooms
|
Conference | 1/28/2008 | 1/28/2008 | 1/28/2008 | P | DONE |
Jack Frank
|
|
|
Contact is Brian Cornell. St. Mark''s School Addition. We would like to be onsite at time of inspection. Please call us, maybe 30-60 minutes before your arrival and we will head to the site. Brian=###-#### or Jay ###-####. Thank you. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery conference on new p/s refeeding old p/s that will become sub gear, and outside feeder and grding to seperate building
|
Electrical Rough-In | 12/7/2007 | 12/7/2007 | 12/7/2007 | P | PART |
Mike Kinnear
|
|
|
Contact is Brian Cornell. This inspection is to inspect the 2-in conduit underground panel feeds on the West side of the building before we bury them. Call Brian with any questions. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok cover part under ground conduit from building to transformer about 40ft to transformer from building. 6ft from building is to be covered with concrete.
|
Temporary Service | 12/3/2007 | 12/3/2007 | 12/3/2007 | A | FAIL |
Jack Frank
|
|
|
Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery called needs seperate permit for t/s
|
Temporary Service | 11/29/2007 | 11/29/2007 | 11/29/2007 | P | FAIL |
Mike Kinnear
|
|
|
Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery no grounding electrode --- grounding & grounded conductors need to be terminated on the same bus bar note reinspection fee for no grounding electrode.
|
Temporary Service | 11/28/2007 | 11/29/2007 | 11/28/2007 | A | CANC |
Jack Frank
|
|
|
Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery Inspection cancelled from web by: Richard Montgomery
|
Rough-In Permanent Service | 11/21/2007 | 11/21/2007 | 11/21/2007 | P | PART |
Jack Frank
|
|
|
Contact is Brian Cornell. This is to inspect the conduit for the service prior to burying the conduit. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok
|