ELE-Aging Inspection | 11/10/2008 | 11/10/2008 | 11/10/2008 | | DONE |
Bob Reichert
|
|
|
looked at sign, see final, no esc this project
|
Final | 11/10/2008 | 11/10/2008 | 11/10/2008 | A | PASS |
Bob Reichert
|
|
|
looked at signs, ok to final, no esc this project
|
Final | 5/21/2008 | 5/21/2008 | 5/21/2008 | A | FAIL |
Jack Frank
|
|
|
corr left correction with general for sign company he called them, 600.5(C)(3)&410.15(B) needs handhole and grd terminal, 314.3 shall not use metallic RMC nipple with non-metallic unless it meets code noted bell bos at sign, 342.46 shall use bushings all RMC nipples used at sign
|
ELE-Aging Inspection | 2/20/2008 | 2/20/2008 | 2/20/2008 | | DONE |
Bob Reichert
|
|
|
suc
|