Final | 3/25/2008 | 3/26/2008 | 3/26/2008 | A | PASS |
Bob Reichert
|
|
|
Lock box combo is 1290. Any questions or concerns please call Clay at ###-####. Thanks. Phone #: ###-#### Internet Inspection Request from: Clay Morgan people moved in, no access to all receptacles, rest ok, ok to final
|
Permanent Service | 12/6/2007 | 12/7/2007 | 12/7/2007 | A | PASS |
Mike Kinnear
|
|
|
Access code is 1290. Any questions or concerns please call Clay at ###-####. Thanks. Phone #: ###-#### Internet Inspection Request from: Clay Morgan p/s o/h reconnect ok
|
Rough-In Permanent Service | 12/2/2007 | 12/3/2007 | 12/3/2007 | A | CANC |
Bob Reichert
|
|
|
Please call for access code. Any questions or concerns call clay at ###-####. Thanks Phone #: ###-#### Internet Inspection Request from: Clay Morgan see nri and p/s
|
Electrical Rough-In | 12/3/2007 | 12/3/2007 | 12/3/2007 | A | PASS |
Bob Reichert
|
|
|
Please call for access code. Any questions or concerns call clay at ###-####. Thanks Phone #: ###-#### Internet Inspection Request from: Clay Morgan ric ok
|
Permanent Service | 12/3/2007 | 12/3/2007 | 12/3/2007 | A | FAIL |
Bob Reichert
|
|
|
Please call for access code. Any questions or concerns call clay at ###-####. Thanks Phone #: ###-#### Internet Inspection Request from: Clay Morgan called contractor, left correction notice, nec 230.24(A)exception 3 reduction in clearance above roof shall be 18" above overhanging portion shall be permitted, 250.104(B) shall bond hot and cold piping at water heater, Note-verify that nec 210.52 does not require receptacles entering kitchen on right and left wall
|