Final | 3/26/2008 | 3/27/2008 | 3/27/2008 | A | PASS |
Bob Reichert
|
|
|
Reinspection. Phone #: ###-#### Internet Inspection Request from: BRENDA HURST corrections made, ok to final
|
Final | 3/19/2008 | 3/20/2008 | 3/20/2008 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: BRENDA HURST called, left correction notice, NEC 408.4 circuit directory shall be clear, concise and explanatory for each circuit, 314.25 in completed installations, each box shall have a cover installed, 410.8 closet light shall be 12" from edge of fixture to edge of shelf
|
Electrical Rough-In | 12/3/2007 | 12/3/2007 | 12/3/2007 | P | PASS |
Bob Reichert
|
|
|
Corrections have been made and job is ready for re-insp. Randi''s # ###-####. Thanks Phone #: ###-#### Internet Inspection Request from: BRENDA HURST called contractor, corrections made, ric ok
|
Electrical Rough-In | 11/29/2007 | 11/30/2007 | 11/30/2007 | A | FAIL |
Bob Reichert
|
|
|
RUFF IN PLEASE, CAN CALL RANDI AT ###-#### Phone #: ###-#### Internet Inspection Request from: BRENDA HURST electricians did not appear to do work, gen contractor met on job, called contrator, left correction notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 334.30 nm cable shall not be stapled on edge, 300.14 at least 6" free conductor shall be left at each box, then made-up, 110.14(A) connection of conductors to terminal parts shall ensure a thoroughly good connection, possible further items will be found at re-inspection, told to provide approved access to upper part
|