Final | 9/3/2008 | 9/4/2008 | 9/4/2008 | A | PASS |
Bob Reichert
|
|
|
Final for project Phone #: ###-#### Internet Inspection Request from: Spencer Mclean corrections made, ok to final, signed occupancy card
|
Electrical Rough-In | 8/25/2008 | 8/26/2008 | 8/26/2008 | A | PART |
Jack Frank
|
|
|
cover inspection for the front recepction desk Phone #: ###-#### Internet Inspection Request from: Spencer Mclean ok
|
Final | 8/8/2008 | 8/8/2008 | 8/8/2008 | A | PART |
Bob Reichert
|
|
|
Final Inspection for entire building Phone #: ###-#### Internet Inspection Request from: Spencer Mclean left correction notice.BCC shall hardwire fixed appliances not readily moveable- heaters, washer, dryer, shall complete x-ray installation for inspection, rest ok, signed t/o card
|
Electrical Rough-In | 8/1/2008 | 8/1/2008 | 8/1/2008 | A | PASS |
Mike Kinnear
|
|
|
inspection for the ceiling cover in the building. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean ok cover ceiling only
|
Electrical Rough-In | 7/30/2008 | 7/31/2008 | 7/31/2008 | A | FAIL |
Jack Frank
|
|
|
Inspection for cieling cover Phone #: ###-#### Internet Inspection Request from: Spencer Mclean corr. needs bushings for low voltage raceways and support, wires for support of cables shall be from structure too grid
|
Permanent Service | 7/16/2008 | 7/16/2008 | 7/16/2008 | P | PASS |
Bob Reichert
|
|
|
spencer Phone #: ###-#### labelled ok, corrections made, p/s u/g n ok
|
Permanent Service | 7/15/2008 | 7/15/2008 | 7/15/2008 | P | FAIL |
Bob Reichert
|
|
|
service inspection Phone #: ###-#### Internet Inspection Request from: Spencer Mclean literature says suitable for service entrance, but no manufacturer label on gear, told electrician that factory has to put on, nobody else can affix label,
|
Permanent Service | 7/2/2008 | 7/3/2008 | 7/3/2008 | P | FAIL |
Bob Reichert
|
|
|
Inspection for perminent service. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean corrections made, but can't find listing "suitable for service" sticker, they will find and recall next week
|
Electrical Rough-In | 7/1/2008 | 7/2/2008 | 7/2/2008 | P | PART |
Jack Frank
|
|
|
Service inspection Phone #: ###-#### Internet Inspection Request from: Spencer Mclean needs to request p/s inspection when ready corr posted met contr 110.26(F)(1) remove water pipe from above subpanel, and 250.104(A)(1) bond all water to p/s gear, terminate main bond and GEC to neutral at p/s
|
Electrical Rough-In | 6/6/2008 | 6/6/2008 | 6/6/2008 | P | PART |
Jack Frank
|
|
|
Underground inspection for the pole lights, and sign conduit. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean all outside u/g ok
|
Electrical Rough-In | 6/6/2008 | 6/6/2008 | 6/6/2008 | A | PART |
Bob Reichert
|
|
|
Underground inspection for the feeders to the sign and light poles Phone #: ###-#### Internet Inspection Request from: Spencer Mclean ok to cover front part u/g anop only- will call for pm for rest, if not open they must dig up
|
Electrical Rough-In | 5/9/2008 | 5/12/2008 | 5/12/2008 | A | PART |
Jack Frank
|
|
|
Rough in for the walls and the hard lids in the main building Phone #: ###-#### Internet Inspection Request from: Spencer Mclean anop electrician's plans
|
Electrical Rough-In | 2/7/2008 | 2/7/2008 | 2/7/2008 | P | PASS |
Bob Reichert
|
|
|
spencer - Note: underground Phone #: ###-#### u/g in main area ok to cover ,concrete encased electrode ok to use from rebar
|
Electrical Rough-In | 2/1/2008 | 2/1/2008 | 2/1/2008 | P | PASS |
Bob Reichert
|
|
|
spencer - underground Phone #: ###-#### u/g ok to cover south side from street to building only
|
Electrical Rough-In | 1/30/2008 | 1/31/2008 | 1/31/2008 | A | FAIL |
Bob Reichert
|
|
|
under ground inspection please-Jeff Phone #: ###-#### called contractor, told to install spacers in u/g cpnduit
|
Electrical Rough-In | 1/18/2008 | 1/18/2008 | 1/18/2008 | P | CANC |
Jack Frank
|
|
|
spencer-upher ground inspection please Phone #: ###-####
|