Final | 2/8/2008 | 2/8/2008 | 2/8/2008 | P | PASS |
Pat Lass
|
|
|
Note: ###-####-former steve for code Phone #: ###-####
|
Final | 2/5/2008 | 2/6/2008 | 2/6/2008 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 2/5/2008 at 2:26:21 PM. Contact: ###-####. needs guy kit , and remove phone , catv from below p/s for clearence , also no access p/s locked called and not ready
|
Final | 2/4/2008 | 2/5/2008 | 2/5/2008 | A | NH |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 2/4/2008 at 12:12:03 PM. Contact: ###-####.
|
Rough-In Permanent Service | 12/20/2007 | 12/21/2007 | 12/21/2007 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 12/20/2007 at 3:22:40 PM. Contact: ###-####. called contractor, left correction notice, nec 334.30(A) rmc shall be securely fastened within 3' of service head for above roof termination of mast, 352.30(A) rnc shall be secured within 3' of grade, 352.30(B) rnc shall be strapped every 5', 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members
|
Electrical Rough-In | 12/21/2007 | 12/21/2007 | 12/21/2007 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 12/20/2007 at 3:22:40 PM. Contact: ###-####. called contr about nail plates, ric ok
|
Rough-In Permanent Service | 12/20/2007 | 12/20/2007 | 12/20/2007 | P | FAIL |
Pat Lass
|
|
|
brian Phone #: ###-#### rail for overhead door rail interferes with working clearance of panel
|