Final | 7/17/2008 | 7/17/2008 | 7/17/2008 | P | PASS |
Bob Reichert
|
|
|
dan Note: call dan for access Phone #: ###-#### ok to final, left survey, NEC 422.11(A) a/c branch corcuit shall be protected according to marked nameplate
|
Permanent Service | 6/26/2008 | 6/26/2008 | 6/26/2008 | P | PASS |
Jack Frank
|
|
|
Daniel Phone #: ###-####p/s u/g new ok
|
Permanent Service | 6/23/2008 | 6/23/2008 | 6/23/2008 | P | FAIL |
Jack Frank
|
|
|
Daniel Phone #: ###-#### corr fee due called isolate grds and neutral at subpanels usw manufactures listed equip grd bus or means, needs equip grd run in pvc nipple to subpanel, protect subpanels cover or cardboard
|
Permanent Service | 5/29/2008 | 5/29/2008 | 5/29/2008 | P | CANC |
Bob Reichert
|
|
|
daniel- for groundwork Phone #: ###-#### called contractor, only needed u/g for duplex ri, will call for p/s later
|
Electrical Rough-In | 5/29/2008 | 5/29/2008 | 5/29/2008 | P | PASS |
Bob Reichert
|
|
|
daniel - groundwork Phone #: ###-#### ok to cover u/g
|
Final | 1/24/2008 | 1/25/2008 | 1/25/2008 | A | CANC |
Jack Frank
|
|
|
daniel Phone #: ###-####
|
Permanent Service | 1/24/2008 | 1/24/2008 | 1/24/2008 | P | FAIL |
Jack Frank
|
|
|
ok per Jack F to send for todaypm ///DLD shall terminate GEC to p/s not subpanels , and shall be #4 copper to electrode called
|
Electrical Rough-In | 1/24/2008 | 1/24/2008 | 1/24/2008 | P | PART |
Jack Frank
|
|
|
daniel Phone #: ###-#### r/i for both units ok still needs r/i for u/g feeder to west side unit
|
Electrical Rough-In | 1/15/2008 | 1/15/2008 | 1/15/2008 | P | FAIL |
Jack Frank
|
|
|
daniel Phone #: ###-#### corr called 110.3(A) laundry outlet romex damaged, 230.2 olny one p/s allowed for duplex, T250.122 needs #12 equip grd pigtail for disposal switch east side, 314.17(A)&C) replace all 2,3,4 gang boxes with broken out internal clamps
|