Permit Information
Permit NumberELE08-00128
StatusFinaled
Name MICHAEL ROWLEY
Site Address 3848 W ROSE HILL ST
Project Nameduplex
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/28/20083/28/20083/28/2008PPASS
DetailsBob Reichert
Michael; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corrections made, ok to final
Final3/25/20083/25/20083/25/2008PFAIL
DetailsBob Reichert
michael Phone #: ###-#### met owner, left correction notice, NEC 406.4(D) receptacles face shall be flush with or project from faceplate, 406.4 receptacles shall be securely fastened in place, 422.31 shall provide lock-outs for dishwashers, BCC all equipment shall be installed- air conditioners, panel screws shall be installed, shall permanently id units at service
Rough-In Permanent Service1/29/20081/29/20081/29/2008PPASS
DetailsBob Reichert
mike Phone #: ###-#### p/s u/g n ok
Electrical Rough-In1/18/20081/18/20081/18/2008PPASS
DetailsBob Reichert
michael Phone #: ###-####Note: come as late as possible please corrections made, ric both sides ok
Electrical Rough-In1/17/20081/18/20081/18/2008AFAIL
DetailsBob Reichert
mike Phone #: ###-#### met owner, left correction notice, nec 314.20 in walls of combustible material, boxes shall be flush with finished surface, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 210.52(A)(2) shall provide receptacle in 2' wall space, 210.52(A)(1) receptacles shall be installed such thatno point in wall line is more than 6' from an outlet, 300.14 at least 6" free conductor shall be left from where conductor enters box for splices or connections
Conference1/15/20081/16/20081/16/2008ADONE
DetailsBob Reichert
Michael Phone #: ###-#### met owner, talked about only him doing work, outlet spacing, box fill , he says he has a code book, when to call for ri inspection, quite a bit of wiring already done, needs make-up and will call for inspection