Final | 3/28/2008 | 3/28/2008 | 3/28/2008 | P | PASS |
Bob Reichert
|
|
|
Michael; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corrections made, ok to final
|
Final | 3/25/2008 | 3/25/2008 | 3/25/2008 | P | FAIL |
Bob Reichert
|
|
|
michael Phone #: ###-#### met owner, left correction notice, NEC 406.4(D) receptacles face shall be flush with or project from faceplate, 406.4 receptacles shall be securely fastened in place, 422.31 shall provide lock-outs for dishwashers, BCC all equipment shall be installed- air conditioners, panel screws shall be installed, shall permanently id units at service
|
Rough-In Permanent Service | 1/29/2008 | 1/29/2008 | 1/29/2008 | P | PASS |
Bob Reichert
|
|
|
mike Phone #: ###-#### p/s u/g n ok
|
Electrical Rough-In | 1/18/2008 | 1/18/2008 | 1/18/2008 | P | PASS |
Bob Reichert
|
|
|
michael Phone #: ###-####Note: come as late as possible please corrections made, ric both sides ok
|
Electrical Rough-In | 1/17/2008 | 1/18/2008 | 1/18/2008 | A | FAIL |
Bob Reichert
|
|
|
mike Phone #: ###-#### met owner, left correction notice, nec 314.20 in walls of combustible material, boxes shall be flush with finished surface, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 210.52(A)(2) shall provide receptacle in 2' wall space, 210.52(A)(1) receptacles shall be installed such thatno point in wall line is more than 6' from an outlet, 300.14 at least 6" free conductor shall be left from where conductor enters box for splices or connections
|
Conference | 1/15/2008 | 1/16/2008 | 1/16/2008 | A | DONE |
Bob Reichert
|
|
|
Michael Phone #: ###-#### met owner, talked about only him doing work, outlet spacing, box fill , he says he has a code book, when to call for ri inspection, quite a bit of wiring already done, needs make-up and will call for inspection
|