Temporary Service | 1/25/2008 | 1/28/2008 | 1/28/2008 | A | PASS |
Jack Frank
|
|
|
Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek t/s u/g new ok
|
Temporary Service | 1/25/2008 | 1/25/2008 | 1/25/2008 | P | FAIL |
Mike Kinnear
|
|
|
Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek corrections NEC312.5 needs proper connector for ground wire & NEC250.24(A)(1) the grounding conduct shall be terminated with grounded conductor on same bus bar. called thecontractor
|