Electrical Rough-In | 3/13/2008 | 3/14/2008 | 3/14/2008 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Smith ok
|
Final | 3/14/2008 | 3/14/2008 | 3/14/2008 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Smith ok
|
Electrical Rough-In | 2/14/2008 | 2/14/2008 | 2/14/2008 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Smith corr. called clearence for new subpanel, boxes of required size for straight thru pulls, 300.4(F) bushings for #4 or larger
|
Final | 2/13/2008 | 2/14/2008 | 2/14/2008 | A | CANC |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Smith Inspection cancelled from web by: Kathy Smith
|