Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE08-00204
StatusFinaled
Name BENCHMARK ELECTRIC CO
Site Address 11427 W EXECUTIVE DR
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Alteration: Wire new panel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Electrical Rough-In3/13/20083/14/20083/14/2008APASS
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Kathy Smith ok
Final3/14/20083/14/20083/14/2008APASS
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Kathy Smith ok
Electrical Rough-In2/14/20082/14/20082/14/2008PFAIL
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Kathy Smith corr. called clearence for new subpanel, boxes of required size for straight thru pulls, 300.4(F) bushings for #4 or larger
Final2/13/20082/14/20082/14/2008ACANC
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Kathy Smith Inspection cancelled from web by: Kathy Smith