Final | 3/24/2008 | 3/24/2008 | 3/24/2008 | P | PASS |
Bob Reichert
|
|
|
anill Phone #: ###-#### corrections made, ok to final
|
Final | 3/6/2008 | 3/6/2008 | 3/6/2008 | P | FAIL |
Jack Frank
|
|
|
jesus Phone #: ###-#### needs outside light fixture installed
|
Electrical Rough-In | 2/12/2008 | 2/13/2008 | 2/13/2008 | P | PASS |
Bob Reichert
|
|
|
isidro Phone #: ###-#### ric ok, corrections made
|
Permanent Service | 2/13/2008 | 2/13/2008 | 2/13/2008 | P | PASS |
Bob Reichert
|
|
|
p/s o/h n ok
|
Electrical Rough-In | 2/11/2008 | 2/11/2008 | 2/11/2008 | P | FAIL |
Bob Reichert
|
|
|
isidra Phone #: ###-#### met people, left correction notice, BCC all make-up shall be done, NEC 352.30(A) shall securely fasten rnc within 3" of conduit termination (above meter), 110.3(b) Shall use listed or labelled equipment (plastic grounding electrode bushing)
|
Final | 2/7/2008 | 2/8/2008 | 2/8/2008 | A | FAIL |
Jack Frank
|
|
|
Isidro Phone #: ###-#### called partial corr. needs r/i p/s not final 300.4 11/4" for cables on edge of 2x6, needs guy kit, needs connector for G E C at panel
|
Conference | 2/5/2008 | 2/6/2008 | 2/6/2008 | A | DONE |
Bob Reichert
|
|
|
isidro-- call 1st before insp Phone #: ###-#### talked about concrete encased electrode, part of new service
|