Permit Information
Permit NumberELE08-00309
StatusCOL
Name ELCOR ELECTRIC
Site Address 855 W BROAD ST Unit: 260
Project Name 
Customer Number29391
ePlanReview 
Description
Electrical Permit - New: ELECTRICAL WORK
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/25/20084/25/20084/25/2008PPASS
DetailsPat Lass
seth Phone #: ###-####
Final4/23/20084/23/20084/23/2008PFAIL
DetailsPat Lass
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen
undersized GEC should be 2/0
check to make sure amplifier is removed from above the ceiling.
Final4/22/20084/22/20084/22/2008PPART
DetailsPat Lass
Please make this as late in the day as possible I would appreciate it. Phone #: ###-#### Internet Inspection Request from: Ryan Christensen
finish grounding make directory spacific and seal coolers. signed T/O
Permanent Service4/21/20084/21/20084/21/2008PCANC
DetailsBob Reichert
Ryan Phone #: ###-#### see conference
Conference4/21/20084/21/20084/21/2008PDONE
DetailsBob Reichert
Ryan Phone #: ###-#### told contractor that address still seems to be problem based on BLD, service is on , but told contractor that transformer is where service starts for low voltage part, that grounding shall be at transformer secondary, and that 800A panel shall be 4-wire with ground and grounded conductor separated
Electrical Rough-In4/17/20084/17/20084/17/2008PFAIL
DetailsPat Lass
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen
supports not perpendicular or connected to grid.
Electrical Rough-In4/16/20084/17/20084/17/2008ACANC
DetailsPat Lass
Ceiling Phone #: ###-#### Internet Inspection Request from: Ryan Christensen
not ready due to job emergency
Electrical Rough-In4/15/20084/16/20084/16/2008PNR
DetailsPat Lass
kitchen ceiling cover Phone #: ###-#### Internet Inspection Request from: Ryan Christensen
require verification from UL fro placement of info sticker on recessed cans and more support of mc cable
Electrical Rough-In4/10/20084/11/20084/11/2008PPASS
DetailsWilliam E Thomas
Ceiling inspection
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen
. .1. cielings ok for cover. . .
. .2. this does not include the kitchen. . .
Electrical Rough-In2/14/20082/15/20082/15/2008PPART
DetailsPat Lass
Please inspect panel locations for cover Phone #: ###-#### Internet Inspection Request from: Ryan Christensen
Panel walls ok
Electrical Rough-In2/8/20082/8/20082/8/2008PPART
DetailsPat Lass
INSPECTION AS LATE IN THE AFTERNOON AS POSSIBLE!

THANK YOU! Phone #: ###-####
Internet Inspection Request from: Ryan Christensen
walls anop oj